The purpose
What does this calculator estimate?
The right breaker size for your pool pump motor, using NEC full-load amps and the 125% continuous-load rule.
Electrical · H1
The right breaker size for your pool pump motor, using NEC full-load amps and the 125% continuous-load rule.
Useful forElectricalPlanningComparisonVerification
Live calculation
✓ Checked May 2026
Enter motor HP, voltage, and type.
Calculated result
—
Enter the required values to calculate.
Enter the known values. Let the engine handle the calculation.
Planning estimate only. Confirm product labels, equipment specifications, qualified-professional advice and local requirements before acting.
The result, explained
The right breaker size for your pool pump motor, using NEC full-load amps and the 125% continuous-load rule.
The purpose
The right breaker size for your pool pump motor, using NEC full-load amps and the 125% continuous-load rule.
The tool
The method
The relationship
Minimum breaker = Full-load amps × 1.25 (continuous-load factor)
FLA from NEC tables 430.248/430.250. Round up to a standard breaker. Pool pumps require GFCI (NEC 680.22).Worked through
| Motor HP | 115V FLA | 230V FLA | 230V breaker |
|---|---|---|---|
| 0.75 HP | 6.9 A | 3.4 A | 15 A |
| 1.0 HP | 8.0 A | 4.0 A | 15 A |
| 1.5 HP | 10.0 A | 5.0 A | 15 A |
| 2.0 HP | 12.0 A | 6.0 A | 15 A |
| 3.0 HP | 17.0 A | 8.5 A | 20 A |
| 5.0 HP | 28.0 A | 14.0 A | 20 A |
Why it matters
Pool pumps count as continuous loads — the NEC requires sizing at 125% of full-load amps.
Always size from nameplate full-load amps, not horsepower alone.
Good inputs
The boundary
Use this as a planning reference only; a licensed electrician and local code determine the installation.
The engine reports invalid inputs and safety warnings beside the result. Resolve those messages before using the estimate.
Before acting
Common questions
Take the motor's full-load amps from the NEC tables, multiply by 1.25 because pool pumps are continuous loads, and round up to the next standard breaker. A 1.5 HP pump on 230V draws about 5 amps, so 5 × 1.25 = 6.25, rounding to a 15-amp breaker — though wire and GFCI requirements must also be checked.
The National Electrical Code defines a continuous load as one operating for three hours or more, and pool pumps qualify. Code requires the circuit be sized to at least 125 percent of the continuous load so conductors and the breaker don't run at their absolute limit for long periods, which prevents overheating.
Yes. NEC 680.22 requires ground-fault circuit-interrupter protection for pool pump motors, because of the severe shock hazard around water. This is a non-negotiable life-safety requirement, provided by a GFCI breaker or GFCI device. Never wire a pool pump without it.
Not directly — you size from full-load amps, which the NEC tables give by horsepower and voltage. Horsepower alone isn't enough because amps depend on voltage and phase too. Use the nameplate or NEC table FLA, apply the 125 percent factor, then select the breaker.
Yes. Pool electrical work involves bonding, GFCI protection, and code rules specific to wet locations, and mistakes can be lethal. Most jurisdictions require a licensed electrician and a permit for pool circuits. Use this calculator for planning and verification, but have the work done and inspected professionally.
On 230V, full-load amps ~5 × 1.25 = 6.25 → a 15-amp breaker, with wire and GFCI checked.
Yes — NEC 680.22 requires GFCI protection for pool pump motors.
They run more than 3 hours, so the NEC requires sizing at 125% of full-load amps.
Primary sources
These official references support safe planning context. Product labels, local requirements and qualified-professional advice take priority over a general calculator estimate.